Note on Occasional DI Failure at Power-On in iS Control Cabinets ​

Problem Description ​

Phenomenon: After the iS control cabinet is powered on, there is a small probability that the DI input fails and the external signal changes cannot be detected.

Problem description: All control cabinets that use the IS3980S chip to detect inputs are affected. Input IOs detected by the IS3980S have a certain risk of failure.

Affected Range ​

Affected control cabinet types: iS control cabinet / iS control cabinet (CE), CSafety control cabinet

Affected firmware versions: 1.0.44-rc.3 (including this version) and earlier; 1.1.11-rc.1 (including this version) and earlier

Problem Resolution ​

If the affected control cabinet has a network connection, the firmware can be downloaded online and installed; without a network, the firmware can be downloaded via a PC (download address: https://download.aubo-robotics.cn/firmware/) and imported via a USB drive.

  1. Fixed firmware versions

v1.0 branch: 1.0.44-rc.4 and above (including this version)

v1.1 branch: 1.1.11-rc.2 and above (including this version)

  1. Firmware upgrade steps

  2. After the upgrade is complete, restart the control cabinet.